Hydraulic Separator 3"
- Home
- Hydraulic Separator 3"
Hydraulic Separator 3"
- Size: 3"
- Input: 90 GPM; 1,300,000 BTU's
- Output: 90 GPM; 1,300,000 BTU's
- Code: SSE-HS-1-250/300
Download PDF
Functionalities
- Operating temperature range: 34-200F°
- Maximum working pressure: 135 PSI
- Minimum working pressure: 7 PSI
- Balances pressure between boiler and central heating loops
- Allows air to be removed from the system via the air extractor on the top
- Provides ports for easy installation of expansion tanks and makeup water, such as a glycol feeder or a boiler feed valve.
- Built in drain port
- Must be installed with di-electric unions
- Eliminates unnecessary fittings in hydronic system
- Easily serviceable